Copper Price 11/19/2024 4.0960
Two element composite cable, 2 conductors 18 AWG unshielded with plenum rated PVC insulation, 1 Pair 22 AWG shielded, with FFEP insulation, with stranded bare copper, and an overall plenum rated PVC jacket. Automation control cable systems (UL) listed CL3P or CMP c(UL)us 75°C
SKU: AVPCRESNT-60/04
 
• Refer to NEC (NFPA 70) article 800 and article 720 for installation guidelines
• UL listed as Type CL3P per UL Standard 13 or as type CMP c(UL)us 75’C per UL Standard 444
• All materials used in the manufacture of this cable are RoHS compliant
• Made in the USA
This spec is for informational purposes and subject to change. This spec may not be suitable for submission. Contact Lake Cable for non-watermark spec sheet.
Products specifications
Attribute nameAttribute value
Conductor - Element 1 18 AWG 2 Conductors Unshielded Plenum rated PVC
AWG Size & Stranding18 AWG, 7 Strands Class B
MaterialAnnealed Bare Copper
Conductor Count2 Conductors
Insulation - Element 1 18 AWG 2 Conductors Unshielded Plenum rated PVC
MaterialPlenum Rated Polyvinylchloride
Wall Thickness0.007”
Color CodeBlack, Red
Conductor - Element 2 22 AWG 1 Pair Shielded with Foam FEP
AWG Size & Stranding22 AWG, 7 Strands Class B
MaterialAnnealed Bare Copper
Conductor Count1 Pair
Insulation - Element 2 22 AWG 1 Pair Shielded with Foam FEP
MaterialFoam Fluorinated Ethylene Propylene (FFEP)
Wall Thickness0.019”
Color CodeBlue, White
Assembly - Element 2 22 AWG 1 Pair Shielded with Foam FEP
Pair Lay LengthCabled on a Common-Axis with Element 1
Pair Drain Wire24 AWG, 7 Strand Tinned Copper (Inside Drain Wire)
Pair ShieldAluminum/Mylar Tape – 100% Coverage (Foil Facing In)
Nominal Electrical Characteristics - Element 2 22 AWG 1 Pair Shielded with Foam FEP
Impedance102 Ω
Capacitance12.8 pF/ft.+/-10%
DC Resistance14.8 Ω/Mft. @ 20°C
Assembly – Elements 1 & 2 - Overall Cable Assembly for Element 1 & 2
Cable Lay Length2.50” LHL Nominal
Jacket – Overall Cable Assembly for Element 1 & 2
MaterialPlenum Rated Polyvinylchloride
Wall Thickness0.015"
Diameter0.184”
ColorTeal/ Yellow Stripe
RipcordYes
Weight31 lbs/Mft
Markings – Overall Cable Assembly for Element 1 & 2
TypeCable permanently identified via surface inkjet print
LegendAVALANCHE BY LAKE CABLE HOME AUTOMATION NETWORK CABLE ROOM A B C D E 0 1 2 3 4 5 6 7 8 9 E171197 18AWG 2C & 22AWG 1PAIR SHIELDED DATA (UL) CMP C(UL)US OR (UL) CL3P 75’C FT-6 (WORK ORDER #) “ROHS”
Footage MarkersYes
Standards - Overall Cable Assembly for Element 1 & 2
Recommended Operating Voltage300V

Remember, all of our wire can feature:

  • Short minumum runs
  • Special jacket colors including stripes
  • Custom print legends
  • Custom cable constructions
  • Custom packaging - boxes or reels
  • Custom lengths
  • Your name on package labels