Copper Price 11/19/2024 4.0960
12 AWG 2 conductor solid bare copper with PE insulation, unshielded with an overall PE jacket 600V, suitable for use in underground conduit or as aerial cable supported by a messenger, for installation in building raceways (not including trays), either as fire protective signaling cable or as traffic signal cable suitable for use in either wet or dry locations.
SKU: IM201122/1
 
• Made in the USA
• International Municipal Signal Association, Inc. - Specification 20-1.
• All materials used in the manufacture of this cable are RoHS compliant
This spec is for informational purposes and subject to change. This spec may not be suitable for submission. Contact Lake Cable for non-watermark spec sheet.
Products specifications
Attribute nameAttribute value
Conductor
AWG Size & Stranding12 AWG Solid
MaterialAnnealed Bare Copper
Conductor Count2 Conductors
Insulation
MaterialPolyethylene
Wall Thickness0.030”
Color CodePer IMSA Specification 20-1, Table 5.1
Assembly
Lay LengthPer IMSA 20-1
FillersNon-Hygroscopic fillers as necessary for a circular cross-section
BinderClear Mylar
ShieldN/A
Drain WireN/A
Jacket
MaterialPolyethylene
Wall Thickness0.045”
Diameter0.374”
ColorBlack
RipcordYes
Weight77 lbs./Mft.
Markings
TypeCable shall be permanently identified via indent print
LegendLAKE CABLE IMSA 20-1 600V (YEAR OF MFG) “ROHS”
Footage MarkersNo
Standards
Operating Temperature Range-40°C to 75°C
DC Resistance, Nominal1.62 Ω/Mft @ 20°C

Remember, all of our wire can feature:

  • Short minumum runs
  • Special jacket colors including stripes
  • Custom print legends
  • Custom cable constructions
  • Custom packaging - boxes or reels
  • Custom lengths
  • Your name on package labels