Copper Price 11/21/2024 4.1235
18 AWG 6 conductor 7 strand bare copper with polyvinylchloride and nylon insulation, unshielded with an overall PVC jacket 600V control tray cable, approved for use in SUN RES DIR BUR 90°C applications.
SKU: V186
 
• Made in the USA
• All materials used in the manufacture of this cable are RoHS compliant
• Refer to NEC (NFPA 70) article 1277 for installation guidelines
• Cable is suitable for use in Class I Division II hazardous locations
• UL listed as Type TC-ER per UL Standard 1277 for tray cables
• UL approved for Direct Burial and Sunlight Resistant applications
• Cable meets UL 1581 & 1202 (FT-4) 70,000 BTU/HR & ICEA T-29-520 210,000 BTU/HR requirements
• Meets ICEA S-73-532, where applicable
This spec is for informational purposes and subject to change. This spec may not be suitable for submission. Contact Lake Cable for non-watermark spec sheet.
Products specifications
Attribute nameAttribute value
Conductor
AWG Size & Stranding18 AWG 7 Strands Class B
MaterialAnnealed Bare Copper
Conductor Count6 Conductors
Insulation
MaterialPolyvinylchloride & Nylon
Wall Thickness0.015” PVC & 0.005” Nylon
Color CodeMethod 1, Table E-2
Assembly
Lay LengthPer UL Standard 1277
FillersN/A
BinderN/A
ShieldN/A
Drain WireN/A
Jacket
MaterialPolyvinylchloride
Wall Thickness0.045”
Diameter0.340”
ColorBlack
RipcordYes
Cold Bend Rating-40°C
Weight76 lbs./Mft.
Markings
TypeCable shall be permanently identified via surface inkjet print
LegendLAKE CABLE E208309 18AWG 6C (UL) TC-ER PVC/NYLON 600V 90’C DRY/WET PVC JACKET SUN RES DIR BUR FT4 “ROHS”
Footage MarkersYes

Remember, all of our wire can feature:

  • Short minumum runs
  • Special jacket colors including stripes
  • Custom print legends
  • Custom cable constructions
  • Custom packaging - boxes or reels
  • Custom lengths
  • Your name on package labels